GSTIN 27ANQPP7409M1Z5 · Pan-India service · HQ Pune sales@powersolutions.net.in ☎ +91 86054 45290

What size DG set do you need?

List the loads, say how each motor starts, and get an honest rating — sized for starting surge, engine kW and UPS or drive loading, snapped to the real Cummins ladder, and confirmed free by an engineer before you commit.

How the maths works

  1. Running load, at each load’s own power factor. Motor HP and kW are shaft ratings, so input power is shaft ÷ efficiency (typical IE2/IE3 values from IEC 60034-30-1), then kVA at the motor’s running PF. Heaters sit at unity; lighting and IT at 0.9; air conditioning from tons at typical BEE input figures. kW and kVAR are summed as a vector, then the growth margin is applied.
  2. Continuous headroom — kVA and kW. Running load should sit near 75% of the prime rating: ISO 8528-1 caps a prime-rated set’s 24-hour average at 70%, and Cummins advises never running below 30%. Because every set is rated at 0.8 PF, a high-PF load (heaters, IT) can run out of engine kW before alternator kVA — the calculator checks both.
  3. The largest motor starts last. Cummins application practice: size for the largest cycling motor starting with everything else already running. Its impact kVA follows Stamford AGN090 — 7× running kVA direct-on-line (6× above 250 kW), 3× star-delta, DOL × the tap fraction squared on an auto-transformer (an 80% tap gives 4.5×), ~3.5× at a typical soft-starter current limit, a 1.2× ramp on a drive.
  4. Alternator transient capability at your allowed dip. AGN090: a well-designed Class-H alternator supplies about 175% of its rating at a 25% transient voltage dip. The dip is set by subtransient reactance, so that figure is scaled to the dip you allow — roughly 0.9× at 15%, 1.3× at 20%, 2.3× at 30%, 2.8× at 35%. Tighter dip, bigger set.
  5. Engine kW during the start. Starting power factor is very low — 0.1–0.15 on DOL, 0.4 on star-delta (AGN090) — so the engine sees far less kW than the surge kVA suggests. That kW, plus everything else running, must fit within the prime rating’s 10% overload.
  6. Non-linear loads and site derate. Cummins PT-7007: keep drive loads under ~50% of capacity; carry rectifier loads at 1.15× nameplate for 12-pulse inputs and far more for 3-pulse. Above 1,000 m and 40 °C the set’s output shrinks (ISO 3046 derating), so the requirement is grossed up to compensate. The largest of all six demands governs, rounded up to the Cummins ladder.

Worked example

A warehouse runs 12 kW of lighting and sockets plus a 20 HP compressor on a direct-on-line starter. The compressor’s shaft power is 14.9 kW; at 90% efficiency and 0.85 PF it draws 16.6 kW and 19.5 kVA running. Running load with 10% growth: 36 kVA. Headroom check: 36 ÷ 0.75 = 48 kVA. Starting check: the compressor’s impact is 7 × 19.5 = 136.5 kVA, on top of 14.7 kVA of lighting already running — 151 kVA, which at a 25% dip needs 151 ÷ 1.75 = 86 kVA of alternator. Starting governs, so the answer is not a 50 kVA set but the next rating above 86 — a 100 kVA Cummins, running at 36% load. Fit a soft starter to the compressor and the same site sizes at 62.5 kVA.

Sizing, answered

Frequently asked questions

Why does the calculator ask how each motor starts?

Because starting current — not running load — usually decides the rating. A direct-on-line motor draws roughly seven times its running kVA for a few seconds; a star-delta starter cuts that to about three times; a VFD nearly eliminates it. Two sites with identical running loads can need very different gensets.

Why is the recommended set bigger than my total load?

Two reasons: a genset should not run continuously at the top of its prime rating (sizing so running load sits near 75% leaves margin for surges and future loads), and the set must absorb the largest motor’s starting surge without a damaging voltage dip. The calculator sizes for both, plus engine kW and any UPS or drive loading, and tells you which one governed.

What is "allowed voltage dip", and which value should I pick?

It is how far the voltage may sag for a moment when the biggest motor starts. Stamford’s guidance allows 35% at the motor but reserves 10% for cabling, leaving 25% for the set — the default. Many consulting engineers specify 20% for mixed loads; medical imaging and other sensitive electronics call for 10%. A tighter dip always means a bigger set, because the alternator can deliver less starting kVA before it sags that far.

Why do UPS units and variable-speed drives make the set bigger?

Their rectifier inputs draw distorted current, which heats the alternator and distorts the voltage for everything else. Cummins guidance keeps drive loads under about half of generator capacity to hold distortion below 15%, and sizes rectifier loads at 1.15 times nameplate for 12-pulse inputs, rising steeply for older 6-pulse designs. The calculator applies those factors rather than the plain arithmetic.

Can a genset be too big for my load?

Yes, and it is an expensive mistake twice over. Cummins application guidance is not to run a diesel set below about 30% of rated load for sustained periods: chronic light running glazes cylinder bores and passes unburnt fuel into the exhaust (wet stacking), which shows up later as slobber, fouled injectors and shortened life. If a starting surge forces a set your running load will barely touch, the calculator shows what a soft starter on that motor would save.

Does the order in which loads start change the size I need?

Dramatically. Starting everything in one step forces the set to swallow every surge at once; stepped starting — largest motor first, then the rest — usually allows the smallest set for the same steady load. Two rules from Cummins application practice: life-safety loads may have to be up within about ten seconds of mains failure, and any motor that cycles on and off in service must be checked as if it starts last, with everything else already running — which is exactly what this calculator assumes.

Is this calculation enough to place an order?

No — treat it as a well-informed starting point. It does not know your motors’ actual code letters, your alternator’s exact transient curve, phase balance, or whether a compressor starts loaded. Send the load list on WhatsApp and an engineer confirms the sizing free of charge, the same day, against the Cummins data sheet for the specific model.

Reply within 4 working hours. Engineered offer within 24 hours.